Group 11: Fan and Pump Control Parameters
Chapter 5 Parameters|VFD-B Series
11 - 00 V/f Curve Selection
Settings
Factory Setting: 00
00 V/f curve determined by Pr.01-00 to Pr.01-06.
01 1.5 power curve
02 1.7 power curve
03 Square curve
04 Cube curve
Confirm the load curve and select the proper V/f curve before use.
The available V/f curves are shown below:
01-02
Voltage100%
100
1.5 power curve
90
80
1.7 power curve
70
60
Square power curve
50
40
Cube
power
curve
30
20
10
0
20
40
60
01-01
Freq. %
80 100
V/F Curve Diagram
11 - 01 Start-up Frequency of the Auxiliary Motor
Settings
0.00 to 400.00 Hz
Unit: 0.01
Factory Setting: 0.00
This parameter serves as a reference for the startup value of the auxiliary motor. If the setting
is 0, the auxiliary motor cannot be activated.
11 - 02 Stop Frequency of the Auxiliary Motor
Settings
0.00 to 400.00 Hz
Unit: 0.01
Factory Setting: 0.00
When the output frequency reaches this parameter value, the auxiliary motor will be stopped.
There must be a minimum of 5 Hz difference between the start frequency and stop frequency
of auxiliary motor. (Pr.11-01-Pr.11-02) > 5 Hz.
11 - 03 Time Delay before Starting the Auxiliary Motor
Settings
0.0 to 3600.0 sec
Unit: 0.1
Factory Setting: 0.0
Revision July 2008, BE16, SW V4.08 & V5.00
5-101