Chapter 5 Parameters|VFD-B Series
The base is Pr.01-00. When in PID feedback control, if | Source of PID reference target -
feedback | > Pr.10-16 and exceeds Pr.10-08 detection time, the AC drive will operate
according to Pr.10-09.
10 - 10 PG Pulse Range
Settings
1 ~ 40000 (Max=20000 for 2-pole motor)
Unit: 1
Factory Setting: 600
A Pulse Generator (PG) or encoder is used as a sensor that provides a feedback signal of the
motor speed. This parameter defines the number of pulses for each cycle of the PG control.
For PG or encoder feedback an option PG-card is needed.
10 - 11 PG Input
Settings
00 Disable PG
01 Single phase
02 Forward / Counterclockwise rotation
03 Reverse / Clockwise rotation
Factory Setting: 00
The relationship between the motor rotation and PG input is illustrated below:
FWD
REV
PULSE
PG
GENERATOR
A phase leads B phase
A phase
CCW B phase
10-11=02
B phase leads A phase
A phase
CW
B phase
10-11=03
A phase
CW B phase
10 - 12 ASR (Auto Speed Regulation) control (with PG only) (P)
Settings
0.0 to 10.0
Unit: 0.1
Factory Setting: 1.0
This parameter specifies Proportional control and associated gain (P), and is used for speed
control with PG (encoder) feedback.
NOTE
The parameter can be set during operation for easy tuning.
Revision July 2008, BE16, SW V4.08 & V5.00
5-99