Chapter 5 Parameters|VFD-B Series
Content Address
2100H
2101H
Status
monitor
Read only
2102H
2103H
2104H
2105H
2106H
2107H
2108H
2109H
210AH
210BH
210CH
210DH
210EH
210FH
2110H
2200H
Function
12: Current exceeds 2 times rated current during steady state
operation (ocn)
13: Ground Fault (GFF)
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Base Block
18: Overload (oL2)
19: Auto accel/decel failure (cFA)
20: Software protection enabled (codE)
21: EF1 Emergency stop
22: PHL (Phase-Loss)
23: cEF (Preliminary count value attained, EF active)
24: Lc (Under-current)
25: AnLEr (Analog feedback signal error)
26: PGErr (PG feedback signal error)
Status of AC drive
LED: 0: light off, 1: light up
00: RUN LED
Bit 0-4
01: STOP LED
02: JOG LED
03: FWD LED
04: REV LED
Bit 5
0: F light off, 1: F light on
Bit 6
0: H light off, 1: H light on
Bit 7
0: ā€œuā€ light off, 1: ā€œuā€ light on
Bit 8
1: Master frequency Controlled by communication
interface
Bit 9
1: Master frequency controlled by analog signal
Bit 10
1: Operation command controlled by
communication interface
Bit 11
1: Parameters have been locked
Bit 12
0: AC drive stops, 1: AC drive operates
Bit 13
1: Jog command
Bit 14-15 Reserved
Frequency command (F)
Output frequency (H)
Output current (AXXX.X)
DC-BUS Voltage (UXXX.X)
Output voltage (EXXX.X)
Step number of Multi-Step Speed Operation
Step number of PLC operation
Content of external TRIGGER
Power factor angle
Estimated torque ratio (XXX.X)
Motor speed (rpm)
PG pulse (low word) /unit time (Pr.10-15)
PG pulse (high word) /unit time (Pr.10-15)
Output power (KW)
Reserved
Feedback Signal (XXX.XX %)
5-92
Revision July 2008, BE16, SW V4.08 & V5.00