RTU mode:
Command message:
Address
01H
Function
10H
Starting data
05H
address
00H
Number of data
00H’
(count by word)
02H
Number of data
04
(count by byte)
The first data
13H
content
88H
The second data 0FH
content
A0H
CRC Check Low
‘4D’
CRC Check High ‘D9’
Chapter 5 Parameters|VFD-B Series
Response message:
Address
01H
Function
10H
Starting data address 05H
00H
Number of data
00H
(count by word)
02H
CRC Check Low
41H
CRC Check High
04H
3.4 Check sum
ASCII mode:
LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of
the bytes from ADR1 to last data character then calculating the hexadecimal representation of the
2’s-complement negation of the sum.
For example, reading 1 word from address 0401H of the AC drive with address 01H.
STX
‘:’
Address 1
‘0’
Address 0
‘1’
Function 1
‘0’
Function 0
‘3’
‘0’
Starting data address
‘4’
‘0’
‘1’
‘0’
Number of data
‘0’
‘0’
‘1’
LRC Check 1
‘F’
LRC Check 0
‘6’
END 1
CR
END 0
LF
01H+03H+04H+01H+00H+01H=0AH, the 2’s-complement negation of 0AH is F6H.
RTU mode:
Address
01H
Function
03H
Starting data address
21H
02H
Revision July 2008, BE16, SW V4.08 & V5.00
5-89