Chapter 5 Parameters|VFD-B Series
Group 8: Special Parameters
08 - 00 DC Brake Current Level
Settings
00 to 100%
Unit: 1
Factory Setting: 00
This parameter sets the level of DC Brake Current output to the motor during start-up and
stopping. When setting DC Brake Current, the Rated Current (Pr.00-01) is regarded as 100%.
It is recommended to start with a low DC Brake Current Level and then increase until proper
holding torque has been attained.
08 - 01 DC Brake Time during Start-up
Settings
0.0 to 60.0 sec
Unit: 0.1
Factory Setting: 0.0
This parameter determines the duration of the DC Brake current after a RUN command. When
the time has elapsed, the AC motor drive will start accelerating from the Minimum Frequency
(Pr.01-05).
08 - 02 DC Brake Time during Stopping
Settings
0.0 to 60.0 sec
Unit: 0.1
Factory Setting: 0.0
This parameter determines the duration of the DC Brake current during stopping. If stopping
with DC Brake is desired, Pr.02-02 Stop Method must be set to 00 or 02 for RAMP stop.
08 - 03 Start-Point for DC Brake
Settings
0.00 to 400.00Hz
Unit: 0.01
Factory Setting: 0.00
This parameter determines the frequency when DC Brake will begin during deceleration.
Output Frequency
Run/Stop
Start-Point for
DC Brake
Time during
01-05 Stopping08-03
Minimum Output
Frequency
DC Brake Time
during Stopping
ON
OFF
5-74
Revision July 2008, BE16, SW V4.08 & V5.00