Chapter 5 Parameters|VFD-B Series
06 - 06 Electronic Thermal Overload Relay Selection (OL1)
Factory Setting: 02
Settings
00 Operate with a Standard Motor (self-cooled by fan)
01 Operate with a Special Motor (forced external cooling)
02 Operation disabled
This function is used to protect the motor from overloading or overheating.
06 - 07 Electronic Thermal Characteristic
Unit: 1
Settings
30 to 600 sec
Factory Setting: 60
The parameter determines the time required for activating the I2t electronic thermal protection
function. The graph below shows I2t curves for 150% output power for 1 minute.
Operation
time(min)
5
60Hz or more
4
50Hz
3
10Hz
2
5Hz
1
Load
0 20 40 60 80 100 120 140 160 180 200 factor (%)
06 - 08 Present Fault Record
06 - 09 Second Most Recent Fault Record
06 - 10 Third Most Recent Fault Record
06 - 11 Fourth Recent Fault Record
Readings 00 No fault
01 Over-current (oc)
02 Over-voltage (ov)
03 Overheat (oH)
04 Overload (oL)
05 Overload1 (oL1)
06 External fault (EF)
Factory Setting: 00
5-68