Chapter 5 Parameters|VFD-B Series
Example 1 (Pr.05-15 = 1): Execute one cycle of the PLC program. The parameter settings are:
1. Pr.05-00 to 05-14: 1st to 15th speed (sets the frequency of each speed)
2. Pr.04-04 to 04-09: Multi-Function Input Terminals (set one multi-function terminal as 14 - PLC
auto-operation).
3. Pr.03-00 to 03-03: Multi-Function Output Terminals (set a Multi-Function Terminal as 10-PLC
running indication, 11-PLC step completed and/or 12-PLC program completed).
4. Pr.05-15: PLC mode setting.
5. Pr.05-16: Direction of operation for the 1st to 15th speed.
6. Pr.05-17 to 05-31: Operation time setting of the 1st to 15th speed.
Frequency
05-07
05-06
05-08
05-05
05-09
05-04
05-10
05-03
05-02
05-11
05-12
05-01
05-13
05-00
05-14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
05-17 05-19 05-21 05-23 05-25 05-27 05-29 05-31
multi-function input terminals
05-18 05-20 05-22 05-24 05-26 05-28 05-30
Program operation OFF
ON
command
multi-function output terminals
Program operation OFF
ON
indication
Step operation indication
multi-function output terminals OFF
Program operation fulfillment indication
multi-function input terminals OFF
Time
NOTE
The above diagram shows one complete PLC cycle. To restart the cycle, turn the PLC program off
and on again.
5-60
Revision July 2008, BE16, SW V4.08 & V5.00