04 - 04 Multi-function Input Terminal (MI1)
04 - 05 Multi-function Input Terminal (MI2)
04 - 06 Multi-function Input Terminal (MI3)
04 - 07 Multi-function Input Terminal (MI4)
04 - 08 Multi-function Input Terminal (MI5)
04 - 09 Multi-function Input Terminal (MI6)
Chapter 5 Parameters|VFD-B Series
Factory Setting: 01
Factory Setting: 02
Factory Setting: 03
Factory Setting: 04
Factory Setting: 05
Factory Setting: 06
Settings
Function
Description
00 No Function
Any unused terminals should be programmed to 0 to
insure they have no effect on operation.
01
Multi-Step Speed Command 1 These four inputs select the multi-speed defined by
Pr.05-00 to Pr.05-14 as shown in the diagram at the
end of this table.
02 Multi-Step Speed Command 2
NOTE: Pr.05-00 to Pr.05-14 can also be used to
03 Multi-Step Speed Command 3 control output speed by programming the AC motor
drive’s internal PLC function. There are 17 step
speed frequencies (including Master Frequency and
04 Multi-Step Speed Command 4 Jog Frequency) to select for application.
05 External Reset (N.O.)
06 Accel/Decel Inhibit
The External Reset has the same function as the
Reset key on the Digital keypad. After faults such as
O.H., O.C. and O.V. are cleared this input can be
used to reset the drive.
When the command is active, acceleration and
deceleration is stopped and the AC motor drive
maintains a constant speed.
07
Accel/Decel Time Selection
Command 1
08
Accel/Decel Time Selection
Command 2
Used to select the one of four Accel/Decel Times
(Pr.01-09 to Pr.01-12, Pr.01-18 to Pr.01-21). See
explanation at the end of this table.
Revision July 2008, BE16, SW V4.08 & V5.00
5-53