Chapter 5 Parameters|VFD-B Series
03 - 10 Desired Frequency Attained 2
Settings
0.00 to 400.00 Hz
Unit: 0.01
Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained 1 or 2
(Pr.03-00 to Pr.03-03 = 09 or 22), then the output will be activated when the programmed
frequency is attained.
Fr equ ency
ma ster
fre quency
2 Hz
detection range
des ir ed
frequency waiting time
for
freque ncy
de t e c t i on
4Hz range
dete ction
- 2Hz ran ge
D C br ake time
dur ing stop
run/s to p
master fr eq. attained
(output signal)
des ire d fr eq. attaine d
settin g 03 ze ro spee d indica tion
ON
OFF
OFF
ON
ON
ON
OF F
OFF
OFF
Time
OFF
ON
se tting 24 zero sp eed indi cation ON
OF F
ON
out put timing chart o f m ultip le func tion ter minals
wh en setti ng to fr equ en cy at tain ed or z ero spe ed in di cation
03 - 05 Analog Output Signal (AFM)
Factory Setting: 00
Settings
00 Analog Frequency Meter (0 to Maximum Output Frequency)
01 Analog Current Meter (0 to 250% of rated AC motor drive current)
02 Output voltage (0 to Pr.01-02)
03 Output frequency command (0 to Maximum Frequency)
04 Output motor speed (0 to the Maximum Frequency)
05 Load power factor (cos90o to 0o)
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
03 - 06 Analog Output Gain
Settings
01 to 200%
This parameter sets the voltage range of the analog output signal.
Unit: 1
Factory Setting: 100
5-44